Switchroom · Thrapp Hill · 2026

A room with a load and no people in it

Thrapp Hill Distribution

Electrical switchgear cabinets in a plant room
This is the one plate on the site that ships ungraded. Its dew point is below the coil surface, so under the treatment there is nothing on it to condense.

A sealed switchroom has a large sensible load and almost no moisture in it. Nobody breathes in there, nothing is cooked in there, and the fresh-air rate is zero because the room does not need one. The air recirculates at about 24 °C and 30% relative humidity, which puts its dew point at 5.4 °C.

The coil surface sits at 11 °C. Air cannot condense on a surface warmer than its own dew point, so this coil takes 20 kW of heat out of the room and not one gram of water. Its sensible heat ratio is 1.00 — not approximately, exactly — and its drain pan is dry every hour of the year.

We fitted the drain anyway, with a float alarm on it. If that alarm ever goes off, something about the room has changed and somebody should be told.

The coil on this job

Coil 02 — sensible only

CCU-1, Thrapp Hill

Close control, full recirculation, sealed room with no fresh-air provision.

air on air off 6 rows · 1,400 l/s 5 10 15 20 25 30 35 40 0 5 10 15 20 25 30 dry bulb °C g/kg saturation coil surface 11 °C dew point 5.4 °C on
Coil schedule for CCU-1, Thrapp Hill
  dry bulb humidity ratio RH enthalpy
Air on 24 °C 5.53 g/kg 30% 38.2 kJ/kg
Air off 12.3 °C 5.53 g/kg 63% 26.3 kJ/kg
Duty 20 kW total 20 kW sensible 0 kW latent SHR 1.00
Condensate none — the coil surface is warmer than the entering dew point, so no water can leave the air

Same problem, different building?

Ring us or book the survey. Either way the first thing we do is measure what is actually happening in the room.